Features:
True double-conversion
Rack mounted and Floor standing tower can be convertible
Patented Mimic LCD of which content can be rotated according to the type of deployment
Digital control guarantees high reliability
Output receptacle control for non critical load shedding capability
ECO mode operation for energy saving
Emergency power off function (EPO)
Generator Compatible
Bypass can be used when UPS is off (Stted in LCD)
Cold start
Input:
Norminal Voltage : 208 / 220 /230 / 240Vac (L+N+PE)
Operating Voltage Range : 110-300Vac @ (0-60%) Load, 120-300Vac @ (60-70%) Load, 140-300Vac @ (70-80%) Load, 160-300Vac @ (80-100%) Load
Operating Frequency Range : 50Hz: 45-55Hz, 60Hz: 55-65Hz Auto Sensing
Power factor : > 0.85 @ 25% Load, >0.95 @ 50% Load, > 0.97 @ 75% Load, > 0.99 @ Nominal Voltage & 100% Load
Output:
Output Voltage : 208 / 220 / 230 /240Vac : 230Vac (Default)
Power Facttor : 0.9
Voltage Regulation : +1%
Efficiency:
AC Mode : 89%
Battery Mode : 85%
ECo mode : 94%
Protection:
Overload Line Mode : 105% -150 %, 30s turn to bypass mode; > 150% 300ms turn to bypass mode
Capacity Battery Mode : 105%-150%, exceed 30s shutdown; > 150% exceed 300ms shutdown
Alarm:
Battery Mode : Sounding every 4 seconds
Battery Low : Sounding every second
Overload : Sounding every 0.5 second
Fault : Continuously Sounding